9.3 Design Flow, Septic & Holding Tanks and Tank Construction
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
9.3 Design Flow, Septic & Holding Tanks and Tank Construction
Key Takeaways Explain This Topic AI
Design wastewater flow is at least 150% of estimated daily flow; a dwelling's combined flow is estimated at 100 gallons per bedroom per day (60 gray and 40 black when segregated).
A holding tank must hold at least 5 times the estimated daily flow or 2,000 gallons, whichever is greater, with its service opening within 25 feet of an all-weather road.
Tank manhole openings are at least 23 inches; septic tank manholes rise to within 6 inches of grade, while those over pumps and holding tank service openings extend at least 4 inches above grade.
Holding tank suction and discharge lines are at least 3 inches with a quick-disconnect service port at least 2 feet above grade, and may not allow gravity or siphon drainage.
Septic tanks are pumped when sludge plus scum equals 1/3 of tank volume; holding tanks when the level is 1 foot below the inlet invert.
Last updated: October 2026
Estimating flow (SPS 383.43 (2) to (6))
- Flow type Equation (B = bedrooms, 2 persons each)
- Combined graywater, clear water and blackwater from a dwelling 100 gallons x B
- Segregated graywater and clear water 60 gallons x B
- Segregated blackwater 40 gallons x B
- Public buildings and places of employment Measured flow or a detailed per-capita or per-use estimate
Design wastewater flow must be at least 150 percent of the estimated daily flow to cover peaks.
Worked example. A 4-bedroom house: estimated flow = 100 x 4 = 400 gpd ; design flow = 400 x 1.5 = 600 gpd . A restaurant on the same POWTS adds its own estimate from the SPS 383 Appendix or metered data. Its grease interceptor for a POWTS must be at least 1,000 gallons (SPS 382.34 (5)).
General design requirements (SPS 383.43 (8))
Gravity piping between components: at least 1 ft/s computed velocity at half full.
Pressurized piping upstream of in situ soil components: at least 2 ft/s .
Gravity piping inside an in situ soil component: level, or pitched downstream no more than 4 inches per 100 feet .
Alarms : mechanical treatment or distribution devices need an automatic visual or audible failure alarm on a circuit separate from the device. Pump alarms stay on until manually silenced, and duplex pumps must switch over automatically. A holding tank needs an alarm that warns when servicing is needed.
Tanks in saturated soil must be anchored against flotation . Components inside buildings must be gastight .
Every component that needs maintenance must be accessible .
Tank construction (SPS 384.25)
Topic Requirement
Watertightness, concrete with cover Hold a vacuum of 2 in. Hg for 60 minutes , or hold water for 1 hour after a 24-hour soak and refill to the top of the cover
Watertightness, steel with cover 5 psig air for 15 minutes, or 5 psig water for 60 minutes
Concrete durability Protective coating above the lowest liquid level, or concrete with a water-cement ratio of 0.45 or less
- Steel Coated inside and out; buried tanks need cathodic protection (UL 1746 or STI-P3)
- Venting Every tank (except camping-unit transfer containers) vents gases; vent terminals per SPS 382.31 (16)
- Manholes At least 23 inches in least dimension
Septic (anaerobic) tanks below ground Manhole over the inlet of the first compartment, in each compartment, and over all treatment apparatus and pumps; manholes within 6 inches below grade , but those over apparatus and pumps at least 4 inches above grade
Holding tank service openings At least 4 inches above grade , at least 23 inches, over any pumps or siphons
Security Covers at or above ground on openings larger than 8 inches need locking devices or other effective measures
Warning label Covers on openings over 8 inches get a permanent warning label, at least 4 x 5 inches , lettering at least 1/2 inch
Tank labels Manufacturer, capacity of each compartment or model number; NSF 40 aerobic units carry 2 label plates with rated daily flow
Holding tanks (Holding Tank Component Manual, version 2.1, May 2022, valid through May 2027)
- Specification Requirement
- Capacity 5 x estimated daily flow, or 2,000 gallons, whichever is greater
- Service access Farthest service opening or pump-out port within 25 feet of an all-weather road
- Alarm High-level warning per SPS 383.43 (8) (e) 2. and SPS 384.25 (10)
- Vent 2-inch inside diameter, Table 384.30-1 material, opening oriented down
- Setbacks Table 383.43-1
Service lines (SPS 383.43 (8) (j)):
Suction and discharge lines at least 3 inches .
A quick-disconnect service port with a removable plug, at least 2 feet above grade , labeled with a permanent sign and secured to a support.
The line may not allow the tank to drain by gravity or siphon .
A lift station discharge may be 2 inches , with a keyed switch at the port.
Worked example. A seasonal cabin with 2 bedrooms: estimated flow 200 gpd, and 5 x 200 = 1,000 gallons. The 2,000-gallon minimum is greater, so the tank must hold 2,000 gallons . A 6-bedroom lodge (600 gpd) needs 5 x 600 = 3,000 gallons . Above 3,000 gpd design, plan review moves from the county to the department or a designated agent (Table 383.22-2).
When tanks must be pumped (SPS 383.54 (3) and (4))
- Tank Service trigger
- Anaerobic treatment (septic) tank When combined sludge and scum equal 1/3 of tank volume
- Holding tank When wastewater reaches 1 foot below the inlet invert
- RV transfer tank Serviced so nothing discharges to soil or ground surface
These triggers apply to systems installed before July 1, 2000 as well. The management plan must specifically address servicing if a tank bottom is more than 15 feet below the servicing pad elevation or more than 150 feet horizontally away. Servicing is done by licensed septage operators under NR 113 and NR 114.
Grease and remodels
Kitchen and food wastes from non-dwelling occupancies on a POWTS pass through a grease interceptor of at least 1,000 gallons. In remodels where separating kitchen and toilet waste isn't practicable, the combined waste may go to a POWTS tank sized with the interceptor capacity added to the septic tank capacity (SPS 382.34 (5) (b) 2.).