2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
Key Takeaways Explain This Topic AI
Table 382.30-3 lets a 4-inch building drain or sewer carry 180 dfu at 1/8 inch per foot, 216 at 1/4 inch and 250 at 1/2 inch; 1/16-inch pitch is permitted only at 8 inches and larger.
A gravity-flow sanitary building sewer must be at least 4 inches in diameter; pressurized sewers must be at least 2 inches for ejectors and sewage pumps and 1-1/4 inches for grinder pumps.
The top of a building sewer must be at least 42 inches below finished grade, or 18 inches where it discharges to a septic tank, holding tank or grease interceptor.
Frost protection is required where the sewer top is less than 60 inches below a snow-cleared surface or less than 42 inches below a surface not cleared of snow.
Buried nonmetallic sewers draining to municipal mains need locating means, such as 18-gauge insulated copper tracer wire with green insulation within 6 inches above the pipe.
Last updated: October 2026
Definitions that drive the answer
Building drain : horizontal piping within or under the fully enclosed part of a building, below the lowest fixture, that drains by gravity to the building sewer (SPS 381.01 (39)).
Building subdrain : the horizontal portion that does not flow by gravity to the sewer, so it discharges to a sump (SPS 381.01 (47)).
Building sewer : the part of the drain system outside the fully enclosed building that conveys discharge to a public sewer, private interceptor main sewer, POWTS or other discharge point (SPS 381.01 (44)).
Private interceptor main sewer : a sewer serving 2 or more buildings that is not part of the municipal system (SPS 381.01 (193)).
Table 382.30-3: building drains, subdrains, sewers and private interceptor main sewers
- Diameter (in.) 1/16 in./ft 1/8 in./ft 1/4 in./ft 1/2 in./ft
- 1-1/4 NP NP 1 1
- 1-1/2 NP NP 3 3
- 2 NP NP 6 9
- 3 NP 36 42 50
- 4 NP 180 216 250
- 5 NP 390 480 575
- 6 NP 700 840 1,000
- 8 1,400 1,600 1,920 2,300
- 10 2,500 2,900 3,500 4,200
NP means not permitted. Pipes 3 to 6 inches cannot be laid at 1/16 inch per foot, and pipes 2 inches and smaller need at least 1/4 inch per foot. Building sewers 12 inches and larger, and private interceptor main sewers 8 inches and larger, follow the municipal criteria in NR 110.13.
Worked example. A commercial building drain carries 200 dfu. At 1/8 inch per foot a 4-inch drain is limited to 180, so it needs 5 inches; at 1/4 inch per foot a 4-inch drain (216) works. Pitch can save a pipe size.
Minimum sizes (SPS 382.30 (4) (b) and (c))
Pipe Minimum
Gravity sanitary building sewer 4 inches (a municipality may require more between the lot line and the public sewer)
- Pressurized sewer, ejector or sewage pump 2 inches and 2 ft/s velocity
- Pressurized sewer, grinder pump 1-1/4 inches and 2 ft/s velocity
- Gravity private interceptor main sewer 4 inches
- Building drain elevation and backwater (SPS 382.30 (11) (b))
Building drains go below the lowest floor on which fixtures may be installed, if the sewer elevation permits.
Where an above-ground building drain discharges to a vertical pipe, it must connect to the building sewer at least 30 inches above the basement floor .
A building drain subject to backflow must be protected by a backwater valve or a sump with pumping equipment. The valve must have full-pipe capacity when open and be readily accessible for cleaning.
A floor that is entirely below grade and has a plumbing fixture or appliance must have a floor drain .
Depth and frost protection (SPS 382.30 (11) (c))
- Condition Requirement
- Minimum depth to top of building sewer 42 inches below finished grade
- Sewer discharging to septic tank, holding tank or grease interceptor 18 inches minimum
- Top less than 60 inches below a surface cleared of snow Frost protection required
- Top less than 42 inches below a surface not cleared of snow Frost protection required
Frost protection is not required: within 30 feet of the building drain where the sewer feeds a holding tank, POWTS tank or grease interceptor under an uncleared surface; where the predicted frost depth (Figure 382.30-1 and Table 382.30-6) doesn't reach the pipe; or for public facilities closed from November 15 to March 15 that are not places of employment.
The approved insulation methods are:
Flat extruded polystyrene : at least 18 inches below grade and at least 6 inches above the pipe. Thickness and width come from Tables 382.30-5 and 382.30-7, and any height above 6 inches is added to the width.
Box method : a 3-sided polystyrene box at least 12 inches below grade, 6 inches above and 6 inches to each side of the pipe.
Lightweight insulating concrete : placed to the spring line, extending 6 inches each side, with the top at least 12 inches below grade.
Trenching, bedding and backfill (SPS 382.30 (11) (e))
Use open-trench work unless a local ordinance or inspector allows otherwise.
Where stone over 1 inch or bedrock is found, excavate 3 inches below grade and bed with material that passes a 3/4-inch sieve , compacted to 90 percent standard Proctor .
Initial backfill extends 12 inches over the pipe , uses material passing a 1-inch sieve , and is placed in lifts of 6 inches or less , well tamped.
Provide at least 36 inches of cover before wheel-loading the trench.
Unstable bottoms: drive sheathing 48 inches below the trench bottom, remove 24 inches of soft material and replace it, or pour a reinforced concrete cradle or slab at least 3 inches thick.
Connections and location rules
A building sewer may not pass under one building to serve another, except for farm buildings on one property or buildings on the same property with a piping document recorded with the register of deeds within 90 days .
If no public sewer connection exists within 3 feet of the designated point, use an approved saddle, a cut-in tee or wye, or for concrete or clay mains a connection encased in at least 3 inches of concrete.
A forced sewer connecting to a pressurized public sewer needs a curb stop, a check valve and an accessible quick disconnect upstream of the check valve.
Separation from wells follows NR 811 and NR 812 .
Tracer wire for nonmetallic sewers: at least 18-gauge insulated single-conductor copper, within 6 inches above the pipe, green insulation, accessible at 400-foot intervals, and conductivity-tested. Warning tape is not a substitute. Recording GPS data with the municipality is an alternative.
Storm and clear water may not discharge to a sanitary building drain connected to a publicly owned treatment works, except as SPS 382.36 (3) allows.