Study guide

2.2 Horizontal Branch Drains, Pitch & Changes in Direction

Wisconsin Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Rules & Code Administration

1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards

2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)

2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers

3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)

3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses

4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices

4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)

5 Chapter 5: Water Supply Systems (SPS 382.40)

5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks

6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)

6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration

7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)

7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances

8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)

8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)

9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping

10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers

11 Chapter 11: Special Plumbing Installations & Water Reuse

11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

2.2 Horizontal Branch Drains, Pitch & Changes in Direction

Key Takeaways Explain This Topic AI

Horizontal branch drains 2 inches or smaller need at least 1/4 inch per foot of pitch; branches larger than 2 inches need at least 1/8 inch per foot.

All horizontal drain piping 4 inches or larger must be pitched to produce a computed velocity of at least 2 feet per second flowing half full.

In Table 382.30-2, a horizontal branch may carry at most 3 dfu at 1-1/2 inches, 6 dfu at 2 inches, 20 dfu at 3 inches and 160 dfu at 4 inches.

Running threads, heel inlets placed horizontally, ledged enlargement chambers and drilling-and-tapping connections are prohibited drain fittings (SPS 382.30 (9) (c)).

Drain piping above food, ice or potable-liquid areas needs sleeves 1 inch above the floor, wall-mounted fixtures, seepage pans and accessible ceilings.

Last updated: October 2026

What counts as a horizontal branch

A horizontal branch drain collects fixture drains and carries them to a stack or a building drain. It is not a building drain, building subdrain, building sewer or private interceptor main sewer. Those are sized with Table 382.30-3 and are covered in section 2.4. Footnote b of Table 382.30-2 says this directly: the "drain piping other than stacks" column does not include building drains, subdrains, sewers or forced discharge piping.

Sizing horizontal branches with Table 382.30-2

  • Pipe diameter (in.) Max dfu, drain piping other than stacks
  • 1-1/4 1
  • 1-1/2 3
  • 2 6
  • 3 20
  • 4 160
  • 5 360
  • 6 620
  • 8 1,400
  • 10 2,500
  • 12 3,900

Three points come up repeatedly:

A 2-inch branch holds 6 dfu . Seven dfu needs a 3-inch branch.

A 3-inch branch holds 20 dfu , and the jump to 4 inches allows 160.

The values are maximums "through any portion" of the pipe, so check the most heavily loaded segment, usually just upstream of where the branch joins the stack.

Minimum trap sizes still come from Table 382.30-1: a lavatory trap is 1-1/4 inches and a shower trap 2 inches. A branch sized from the dfu total alone must still accept those trap outlets.

Minimum pitch (SPS 382.30 (5))

  • Pipe Minimum pitch
  • Horizontal branch drain, 2 in. or less 1/4 inch per foot
  • Horizontal branch drain, larger than 2 in. 1/8 inch per foot
  • Any horizontal drain 4 in. or larger Pitch giving at least 2 ft/s computed velocity flowing half full
  • Building drains and building sewers up to 10 in. Per Table 382.30-3

Building sewers 12 in. and larger, private interceptor main sewers 8 in. and larger NR 110.13 municipal sewer criteria

Campground, RV park and manufactured home community drains Per Table 382.30-3

Worked example. A 40-foot run of 3-inch horizontal branch at the minimum 1/8 inch per foot drops 40 x 0.125 = 5 inches . The same length of 2-inch branch at 1/4 inch per foot drops 10 inches. That drop often decides whether the branch can reach the stack above a basement ceiling.

Changes in direction (SPS 382.30 (8))

Changes in direction must use 45-degree wyes, long or short sweep quarter bends, or sixth, eighth or sixteenth bends (or equivalent combinations). For drain piping 8 inches or smaller, fittings must meet the minimum radii in Table 382.30-4:

  • Pipe (in.) Horizontal to vertical Vertical to horizontal and horizontal to horizontal
  • 1-1/4 1-1/8 2-1/4
  • 1-1/2 1-3/8 2-3/4
  • 2 1-7/8 3-1/4
  • 3 2-7/8 4-1/16
  • 4 3-3/4 4-7/8
  • 5 4-1/2 6-1/2
  • 6 5 7
  • 8 6 8

Three exceptions relax the table for the first 90-degree fitting downstream of certain fixtures:

Lavatory or sink trap, 1-1/2 inch drain: 1-3/4 inch minimum radius, and the fitting must be a tee or quarter bend.

Water closet on 3-inch drain: 2-1/2 inch minimum radius.

Water closet on 4-inch drain: 3-inch minimum radius.

Where blowout-type fixtures are installed back to back, fittings must keep waste from passing from one fixture into the other (SPS 382.30 (8) (b)).

Fittings and connections (SPS 382.30 (9))

Fittings may not retard flow more than normal friction. Specific rulings:

A 4 x 3 inch closet bend or collar reduction is not an obstruction.

The side inlet of a low- or high-pattern tee or bend may not be used as a vent connection when the side inlet is horizontal.

Prohibited for drain piping: a heel inlet bend with the heel inlet horizontal, any fitting with an enlargement chamber or a ledge or shoulder, a reduction in area in the direction of flow, running threads, and connections made by drilling and tapping (unless the department approves).

Pipe saddles must meet SPS 384.30 (5) (d).

Drain piping over food and pool areas (SPS 382.30 (13))

Where drain piping runs below the ceiling of a space where food, ice or potable liquids are prepared, handled, stored or displayed:

Floor penetrations need sleeves bonded to the floor that protrude at least 1 inch above the finished floor, with the annular space sealed.

Fixtures above, except bathtubs and showers, must be wall-mounted ; bathtub waste-and-overflow connections must be made above the floor.

Floor and shower drains above need integral seepage pans .

Cleanouts must extend through the floor above.

Piping that can sweat must be insulated.

The ceiling must be removable or have access panels. Exposed drain piping may not be located over a pool, surge tank or open pool filter unless a trough diverts seepage to an approved discharge point.

Loading diagram... Sizing and installing a horizontal branch