11.1 Health Care & Related Facilities (SPS 382.50)
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
11.1 Health Care & Related Facilities (SPS 382.50)
Key Takeaways Explain This Topic AI
Health care hot water is initiated and stored at 140 degrees F or more, and outlets accessible to patients may not exceed 115 degrees F; limit stops may not be used to achieve that limit.
Patient showers, therapeutic equipment and baths use pressure-balanced and thermostatic valves holding 110 to 115 degrees F, cutting flow to 0.5 gpm or less above 115 degrees F or on cold water loss.
Hospitals need at least 2 water services, connected to different mains where available, each able to serve the full building demand.
Hot water systems are under constant recirculation and disinfected by storage at 140 degrees F with a 124 degrees F return, chlorine (0.5 mg/L), chloramine, chlorine dioxide or another approved method.
Floor drains are prohibited in operating and delivery rooms; cystoscopic room drains need a non-splash flushing bowl.
Last updated: October 2026
Why health care is different
Patients are vulnerable to scalding, waterborne pathogens such as Legionella , and cross-contamination. SPS 382.50 adds requirements on top of the general code for "health care and related facilities." Health care plumbing is reviewed only by the department . Table 382.20-1 line 1 sends all new work, additions and alterations in hospitals, nursing homes, ambulatory surgery centers, renal dialysis centers, CBRFs and inpatient hospices to DSPS regardless of fixture count. Line 5 adds the testable backflow assemblies serving these facilities.
Fixtures and equipment (SPS 382.50 (2))
- Item Requirement
- Ice machines and storage Located where not subject to contamination
- Sterilizers and washer-sanitizers Indirect waste discharging through an air gap
- Water aspirators Approved cross connection control
Spouts at lavatories and sinks accessible to patients Fixed spout discharging at least 5 inches above the flood level rim ; laminar flow where required
Actions for staff, patients, residents and food handlers Hands-free ; wrist blades no longer than 4-1/2 inches , except scrub and clinical sinks at least 6 inches ; single-lever handles allowed
Self-closing lavatory faucets accessible to patients Hot water flow calculated to purge the piping back to the recirculated supply
Floor drains Prohibited in operating and delivery rooms ; allowed in cystoscopic rooms with a non-splash, horizontal-flow flushing bowl
Table 382.50-1 assigns spout and action types room by room (nursing, nursery, surgical and other departments). Psychiatric-care areas where gooseneck spouts endanger patients are exempt from the spout rules.
Water supply (SPS 382.50 (3))
Hospitals must have at least 2 water services , connected to different water mains where more than one is available. Each must be able to supply the total building demand (non-essential additions excepted). A code note warns that two services or a private main may require a check valve under NR 811.
All health care facilities must provide hot and cold water to patient-accessible sinks:
Hot water initiated and stored at 140 degrees F minimum.
Maximum temperature at patient-accessible outlets 115 degrees F .
Hospitals, CBRFs, inpatient hospices and nursing homes must also meet these requirements:
Requirement Detail
Valving One control valve may serve up to 4 patient care units with no more than 2 persons each; intensive care units are individually valved
- Insulation All distribution piping insulated per chs. SPS 361 to 366
- Cold water Supplied to lavatories and sinks in patient rooms
Recirculation Constant recirculation to every hot outlet; with thermal disinfection, uncirculated branches no longer than 3 feet
Temperature control Automatic valves regulate any supply over 140 degrees F to patient-accessible fixtures
Showers, therapy equipment, baths Pressure-balanced and thermostatic valves holding 110 to 115 degrees F , reducing flow to 0.5 gpm or less if the outlet exceeds 115 degrees F or cold pressure is lost
- Limit stops Prohibited as the way to meet the 115 degrees F maximum
- Absolute maximum No outlet over 180 degrees F ; patient-accessible outlets 115 degrees F maximum
- Laminar flow At outlets accessible to patients
- Heat recovery Not allowed on hot water distribution systems
- Expansion tanks Flow-through type with a check valve upstream; any bypass valve closed and locked
Disinfection methods (one is required):
Thermal: storage and circulation initiated at 140 degrees F or more with a return of at least 124 degrees F .
0.5 mg/L residual chlorine .
Chloramine.
Chlorine dioxide.
Another department-approved method, or municipal disinfectant with an approved residual and site approval.
Hot water piping is labeled with the disinfection method :
At the injection point.
Within 5 feet of it.
Every 25 feet within the mechanical room.
On the inside of each mechanical room door.
Lettering is at least 1/2 inch high.
Water management plans are required in facilities with more than 250 occupants . They cover:
- Emergency water contingencies
- Pathogen control
- Routine and emergency disinfection
- The person responsible for water quality
- Periodic flushing
- The hot water balancing valve report
Adult day care centers are also limited to 115 degrees F at participant-accessible outlets.
Related provisions elsewhere
Dialysis : a dialysis machine's indirect waste may discharge to a water closet or lavatory in a single-occupancy patient toilet room through a 1-inch air gap (SPS 382.33 (8) (d) 9.). A dialysis box in a patient room must be lockable , with its receptor sealed when not in use. A hose outlet for a portable dialysis machine in a lockable box is not a cross connection.
Sterilizer rooms : a room containing recessed or concealed sterilizer parts needs a floor drain serving the whole floor (SPS 382.30 (11) (b) 3. b.).
Air admittance valves may not be used in health care facilities (SPS 382.31 (17m)).
Health care appliances must meet the drain, vent, supply and backflow rules of SPS 382 (SPS 384.15).
Worked example
A nursing home renovation adds 10 patient rooms (2 beds each) and a therapy tub room.
Plans go to DSPS , not an agent municipality.
Valving: no more than 4 rooms per control valve.
The therapy tub gets a combination pressure-balanced and thermostatic valve set for 110 to 115 degrees F with high-temperature flow cutback.
The loop is designed for thermal disinfection at 140 degrees F with a 124 degrees F return, so uncirculated branches stay at 3 feet or less.
Every patient sink spout discharges at least 5 inches above the rim.
Handles are wrist blades of 4-1/2 inches or less.