Study guide
11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
Key Takeaways Explain This Topic AI
Table 382.70-1 requires NR 811 and 812 approved sources for drinking, cooking, food, medical and personal hygiene uses; reused water serves only listed nonpotable uses that meet their limits.
Water closet and urinal wastewater may not be reused for drinking water, except through DNR-permitted treatment works or a POWTS with in situ soil (SPS 382.34 (3) (a)).
Nonpotable water treatment devices are listed under NSF/ANSI 350 or 350-1 and need an onsite maintenance log (filters at intervals under 3 months; pumps, valves, tanks and backflow devices at start-up and at least every 12 months).
Stormwater infiltration systems need 5 feet of suitable soil to groundwater or bedrock (10 to 20% fines) or 3 feet (20% fines or more), 1 foot for roof runoff, and must drain within 72 hours.
Infiltration systems are set back 10 feet from buildings, 10 feet from POWTS tanks and storage tanks, 5 feet from POWTS dispersal components and property lines, and 15 feet from in-ground pools.
Last updated: October 2026
The reuse framework
SPS 382.34 (3) (a) allows graywater, stormwater, clear water, blackwater and other approved wastewater to be reused under SPS 382.70. One firm limit applies: wastewater from water closets and urinals may not be reused for drinking water , except through DNR-permitted treatment works or a POWTS with an in situ soil component. SPS 382.70 (3) requires every plumbing system to supply water suitable for its intended use that protects public health and the waters of the state.
Table 382.70-1: plumbing treatment standards (selected)
- Intended use Standard at the outlet
- Drinking, cooking, food processing, pharmaceutical and medical uses NR 811 and 812 approved sources
- Personal hygiene, bathing, showering NR 811 and 812 approved sources
- Automatic fire protection As acceptable to the local authority
- Swimming pool makeup water NR 811 and 812 approved sources
- Cooling water pH 6 to 9; BOD5 under 50 mg/L; TSS under 30 mg/L; free chlorine 1.0 to 10.0 mg/L
Subsurface infiltration and irrigation using reuse water Oil and grease under 15; BOD5 under 30; TSS under 35 mg/L; fecal coliform under 200 cfu/100 mL; 12 in. of medium sand or finer above groundwater or bedrock
- Subsurface irrigation using stormwater Oil and grease under 15; TSS under 60 mg/L
- Surface or spray irrigation using stormwater and clearwater BOD5 under 10; TSS under 5 mg/L
Surface irrigation (not food crops), vehicle and clothes washing, air conditioning, dust control, concrete pH 6 to 9; BOD5 under 10; TSS under 5 mg/L; free chlorine 1.0 to 10.0 mg/L
Toilet and urinal flushing pH 6 to 9; TSS 5 mg/L or less; free chlorine 0.1 to 4.0 mg/L (see the table for BOD)
Uses not listed Contact the department
Chlorine and pH limits apply only to reuse treatment devices. Stormwater standards are annual averages. Industrial and WPDES-permitted discharges are excluded.
Treatment devices and systems (SPS 382.70 (5))
Devices that treat nonpotable water for these uses must be listed under NSF/ANSI 350 or 350-1 (or approved under SPS 384.50), designed per SPS 382.34 (3) (a), and provided with three things.
1. A maintenance log kept onsite by the owner:
- Action Interval
- Inspect, clean and replace filters Less than 3 months
- Verify treatment components meet standards Per manufacturer and department
- Pump, valve and pressure tank operation At start-up and at least every 12 months
- Clean storage tanks; check locks At start-up and at least every 12 months
- Labeling and markings At start-up and at least every 12 months
- Mulch basins As needed to prevent ponding and runoff
- Cross connection control inspection and test At start-up and at least every 12 months
2. An onsite manual with a system diagram, operation and maintenance instructions, shutdown steps, manufacturer contacts, model number and sources for expendable parts.
3. Indelible labeling per NSF 350, visible after installation.
Connecting reuse to the building
Reuse piping and outlets are labeled with purple tags or bands (Table 382.40-1a) at no more than 25-foot intervals. Nonpotable hose bibbs are labeled and have removable handles.
The potable makeup to a reuse system is protected per SPS 382.41. Nonpotable water may feed a treatment device designed to meet Table 382.70-1 (SPS 382.40 (3) (a) 2.).
Water supply piping may be reused only for an equal or higher degree of hazard (SPS 382.22 (4) (b)).
Plan review : onsite residential and commercial water reuse treatment systems (Table 382.20-1 line 7), and stormwater and clearwater detention, treatment and infiltration systems serving public buildings (line 6), go to the department. Agent municipalities may review them if the department authorizes.
Underground stormwater reuse tanks are at least 8 feet from sanitary sewers (SPS 382.36 (7) (d) 9.).
Stormwater and clearwater subsurface infiltration (SPS 382.365)
Topic Requirement
Site and soil evaluation Per SPS 385.40 (3) (a) and 385.30 (1) (c), by a registered soil tester under SPS 305.33 or a licensed soil scientist; also DNR technical standards 1002 and 1004
Influent Table 382.70-1 subsurface infiltration standards
In situ soil separation to groundwater or bedrock 5 feet of suitable soil with 10 to 20% fines; 3 feet with 20% fines or more; measured to mounded groundwater where mounding applies
Roof runoff or equivalently treated water At least 1 foot of material finer than coarse sand
Engineered soil (bioretention) At least 24 inches (18 inches with documentation and approval), above any limiting factor
- Groundwater mounding analysis Required when the system is wider than 15 feet
- Drain-down Within 72 hours ; surface ponding within 24 hours
Orientation Long dimension along the contour; level infiltrative surface below original grade (irrigation excepted)
Installation weather Not on frozen soil; remove snow; stop if the soil rolls into a 1/4-inch wire
Setbacks (Table 382.365-4):
- Feature Setback
- Building 10 ft
- Holding tank or stormwater collection tank 10 ft
- POWTS dispersal component 5 ft
- POWTS holding or treatment component 10 ft
- Property line 5 ft
- In-ground swimming pool 15 ft
- Wells NR 811 and 812
No substance may be discharged into an infiltration system that causes NR 140 groundwater limits to be exceeded at a point of standards application. Deleterious substances must be treated under SPS 382.34 first.
Worked example
A commercial building wants to flush its toilets with harvested roof water.
The system is an onsite water reuse treatment system, so plans go to DSPS (Table 382.20-1 line 7).
The treatment device must be NSF/ANSI 350 listed and deliver pH 6 to 9, TSS of 5 mg/L or less and free chlorine of 0.1 to 4.0 mg/L at the water closets.
The flushing piping is purple-labeled.
The potable makeup to the storage tank uses an air gap or other Table 382.41-1 protection.
The owner keeps the onsite log: filters checked at least every 3 months, and pumps, valves, tank and backflow device annually.