10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38)
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38)
Key Takeaways Explain This Topic AI
All sanitary building subdrains discharge into an approved, vented sump with an airtight cover, at least 25 feet from any water well.
A one-pump sump is at least 24 inches in diameter and a two-pump sump at least 30 inches; the pump must run at least 20 seconds, and the low water level is at least 4 inches above the bottom.
Duplex pumps with alternation and an alarm are required in public buildings where 3 or more water closets or more than 20 dfu enter a sump, and where 2 or more dwellings share a sump.
Grinder pumps need at least 1-1/4 inch discharge; nongrinder pumps serving water closets must pass a 2-inch solid with 2-inch discharge; all ejectors give at least 2 ft/s.
Discharge connects to the gravity drain with a wye, with a full-flow check valve (plus a shutoff valve downstream of each check on duplex systems) and no fixtures on the discharge line.
Last updated: October 2026
Sanitary sumps (SPS 382.30 (10) (a))
All sanitary building subdrains discharge into an approved, vented sump with an airtight cover , placed to receive waste by gravity and at least 25 feet from any water well (or as DNR approves). Removable covers may be penetrated only for the electrical supply, the vent and the pump discharge.
Sump capacity (based on one pump):
Determine peak input in gpm by the water supply fixture unit method for the fixtures draining to the sump. A note allows using the flush-tank conversion.
The sump must let the pump, when started by the lowest "pump on" switch, run at least 20 seconds .
Between the highest "pump on" switch and the inlet, the sump holds the input exceeding pump discharge over a 5-minute peak period, and never less than 3 inches of vertical distance.
Low water level per the manufacturer, but at least 4 inches above the bottom.
One-pump sumps are at least 24 inches in inside diameter; two-pump sumps at least 30 inches .
Ejectors and pumps (SPS 382.30 (10) (b))
- Requirement Detail
- Lifting Automatic ejectors, pumps or another approved method
Duplex required Public building with 3 or more water closets or more than 20 dfu into the sump; or sanitary waste of 2 or more one- or 2-family dwellings into one sump
Duplex controls Automatic alternation, both units running when one can't keep up, and an audible or visual alarm with manual reset for pump failure
- Velocity At least 2 ft/s in the forced discharge
- Grinder pumps At least 1-1/4 inch discharge opening and piping
- Nongrinder pumps serving water closets Pass a 2-inch solid; at least 2-inch discharge
- Other sanitary pumps Rated as effluent pumps; pass a 1/2-inch solid; at least 1-1/4 inch discharge
Discharge connection Wye fitting; on a horizontal drain, the bottom of the wye branch above the horizontal centerline
- Check valve Full-flow check valve in each discharge (except exterior sumps)
- Duplex shutoffs A gate or ball valve downstream of each check valve
- Air relief Air relief valves at high points that trap air
- Prohibited No fixtures connected to the discharge pipe before it enters the gravity drain
Pressurized building sewers from ejectors or pumps are at least 2 inches (1-1/4 inch for grinders) and keep 2 ft/s (section 2.4).
Prefabricated sumps and macerating toilets meet ASME A112.3.4/CSA B45.9 . If the manufacturer doesn't size them, they must handle peak input by the wsfu method. Exterior sumps meet SPS 384.25. Instead of duplex pumps, a simplex exterior system may provide one day of holding capacity above a high-level alarm.
Sump vents (SPS 382.31 (8) and (14) (i))
Interior sanitary sumps are vented to the sump above the inlet, or to the inlet drain within 12 inches of the sump.
Exterior sumps vent per SPS 382.31 (16) (h): 12 inches above grade with a cap or return bend.
Vent size comes from Table 382.31-4 by pump capacity. For example, a 40 gpm pump allows a 1-1/4 inch vent up to 72 ft, 1-1/2 inch up to 160 ft, and 2 inches with no limit. Exterior sump vents are at least 2 inches.
A pneumatic ejector's air relief pipe may not connect to the sanitary, storm or chemical vent system. It is at least 1-1/4 inches (2 inches outdoors) and terminates like a vent.
Air admittance valves may not vent a sump.
Worked example. A basement in a public building has 2 water closets (12 dfu), 2 lavatories (2 dfu) and a floor drain (2 dfu), for 16 dfu. With fewer than 3 water closets and no more than 20 dfu, a simplex system is allowed. Add a third water closet and duplex pumps with alternation and an alarm become mandatory. The sump would then need a 30-inch minimum diameter.
Discharge points (SPS 382.38 and Table 382.38-1)
Wastewater must discharge only to the points Table 382.38-1 allows. Uses not listed are decided by the department case by case. Selected lines:
- Use POWTS Municipal sanitary Municipal storm Ground surface Combined sewer Subsurface dispersal
- Domestic wastewater Yes Yes No No Yes No
- High-efficiency furnace or water heater condensate Yes Yes No No Yes No
Stormwater, groundwater, fire sprinkler test and clearwater Yes Yes, 50 gpd max Yes (DNR permit may be needed) Yes (unless locally prohibited, no nuisance) Yes Yes
- Water heater T&P valve discharge Yes Yes Yes Yes (no nuisance) Yes Yes
- Water treatment device wastewater Yes Yes Yes (permit may be needed) Yes (permit may be needed) Yes Yes
- One- and 2-family garage floor area Yes Yes No Yes (no nuisance) Yes No
- Garage catch basin or oil interceptor, public building Holding tank only Yes No No No No
- Elevator pit drain No No Yes Yes Yes Yes
- Secondary roof drains No No No Yes, separate and observable No No
"Yes" for POWTS means the POWTS was designed for that wastewater. Subsurface dispersal must meet SPS 382.365. Diatomaceous earth pool filter backwash goes only to a POWTS, sanitary sewer or combined sewer.