Study guide
4.3 Indirect & Local Waste Piping, Air Gaps & Receptors
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
4.3 Indirect & Local Waste Piping, Air Gaps & Receptors
Key Takeaways Explain This Topic AI
All indirect and local waste piping must discharge through an air gap or air break into a receptor (SPS 382.33 (7)).
An air gap must be at least twice the pipe diameter for indirect waste piping 1 inch or smaller, and at least 2 inches for larger piping.
Indirect and local waste piping handling sanitary waste may not exceed 30 feet horizontally or 15 feet vertically; gravity indirect waste over 30 inches long needs a trap, but sterilizer waste may not be trapped.
A residential clothes washer standpipe must extend 18 to 36 inches above the trap outlet centerline and terminate 26 to 48 inches above the floor.
A residential dishwasher's indirect waste may not exceed 10 feet developed length, and a standpipe receptor for it must be at least 1-1/2 inches and extend 15 inches above the trap weir.
Last updated: October 2026
Definitions
Indirect waste piping is drain piping that does not connect directly with the drain system. It discharges into the drain system through an air break or air gap into a receptor (SPS 381.01 (131)).
Local waste piping receives the discharge from indirect waste piping and itself discharges through an air break or air gap into a receptor (SPS 381.01 (145)).
Indirect and local waste piping serving equipment of public health concern is plumbing (SPS 382.33 (1) (b)). Table 382.33-1 lists, among others, baptismal founts, bar and soda fountains, boiler blowoff basins, clothes washers, coffee makers, dishwashers, food preparation sinks, ice makers, refrigerated cases and rooms, steam tables, sterilizers, stills and vending machines.
Materials, size, traps and length
- Rule Requirement
- Materials (2) Indirect waste over 30 inches long and all local waste piping must be approved SPS 384 materials
Size (3) Size per SPS 382.30; refrigerated display case piping up to 20 ft may be 1 inch minimum; pressurized discharge sized per manufacturer
Traps (5) Gravity indirect waste over 30 inches long needs a trap, but sterilizer indirect waste may not be trapped ; refrigerated room and case drains are always trapped; sanitary local waste over 30 inches is trapped
- Maximum length (6) Sanitary indirect or local waste: 30 feet horizontal, 15 feet vertical
- Access (4) Installed so it can be flushed and cleaned
- Air gaps and air breaks (SPS 382.33 (7))
- Method Requirement
- Air gap, piping 1 inch or smaller Vertical gap at least 2 x pipe diameter
- Air gap, piping larger than 1 inch At least 2 inches
- Air-gap fittings ASME A112.1.3
- Air break Pipe extends below the flood level rim of the receptor but ends above the trap outlet
An air gap is complete separation and gives the highest protection. An air break lets the pipe enter the receptor but keeps it above the trap outlet, so a backup overflows the receptor rather than the appliance.
Receptors (SPS 382.33 (8))
Waste sinks and standpipes: rim at least 1 inch above the floor .
Floor sinks: a removable metal basket or dome strainer. Waste may not discharge through a traffic grate; it must terminate over an ungrated portion.
Local waste piping may not receive discharge from another local waste pipe.
A plumbing fixture may serve as a receptor only in listed cases. For example: a portable dishwasher or water treatment device to a dwelling kitchen sink or branch tailpiece; a clothes washer or softener to a laundry tray; a T&P relief valve, softener, backflow device, humidifier or furnace condensate to a floor drain riser (with an air break) or to a floor served by a floor drain. In a one- or 2-family dwelling, a T&P valve or water treatment device may discharge through the cover of a clear water sump with a fixed air gap.
Required indirect connections (SPS 382.33 (9))
Boilers, pressure tanks and relief valves discharge through an air gap . Steam pipes may not connect to any part of the plumbing system. Wastewater over 160 degrees F must discharge indirectly, and steam condensate blowdown must be cooled to 160 degrees F first. Clear water discharging to the plumbing system uses an air gap.
Residential clothes washers discharge through an air break to a standpipe:
- Standpipe dimension Requirement
- Height above centerline of trap outlet Not more than 36 inches, not less than 18 inches
- Height above the floor the washer sits on At least 26 inches, not more than 48 inches
- Washers per trap (Table 382.33-2) 2-inch trap: 1; 3-inch trap: 3; 4-inch trap: 4
Washer waste may not go to gutters, troughs, local waste piping or indirect manifolds. A single residential ventless dryer discharging under 1 gpm may share a 2-inch washer box or standpipe. Commercial gravity-dump washers discharge by air break into a receptor or trench sized for one full simultaneous load, through a laundry interceptor.
Dishwashers. All dishwashers discharge to the sanitary system.
Residential : indirect waste no longer than 10 feet developed length. With the air gap or air break below the counter , discharge to a standpipe at least 1-1/2 inches that extends at least 15 inches above the trap weir . With it above the counter , discharge through local waste piping to the sink branch tailpiece above the trap inlet, a standpipe, or the disposer's dishwasher inlet; a hose used as local waste may be no longer than 18 inches .
Commercial : air gap or air break into a trapped and vented receptor, with indirect waste no longer than 30 inches .
Food handling establishments.
Bar and soda fountain sinks may use indirect waste: an untrapped line needs an air gap; a trapped line may use an air gap or air break.
Beer taps, coffee makers and soda dispenser drip pans: air break or air gap.
Novelty boxes, ice compartments and dipper wells: air gap , indirect waste no longer than 30 inches, not combined with other equipment.
Refrigerated rooms and cases: air gap or air break; with an air break the receptor rim is at least 2 inches below the case's strainer.
Enclosed food equipment (urns, steam kettles, potato peelers, vending machines): air gap .
Open culinary sinks for thawing or washing food: an independent connection through an air gap , with the fixture drain upstream of the gap no longer than 30 inches .
Other required air gaps : sterilizers and stills; vent ports of backflow devices discharging to a receptor; indoor pool deck drains to the sanitary sewer. Central vacuum units may use an air gap or air break. Outdoor pool deck drains go to the storm sewer by air gap, air break or grade, with the air break at least 6 inches below the deck.
Elevator pit drains discharge to the storm system through a sump, never by direct gravity connection. The pit-drain inlet to the sump is submerged to keep a 6-inch seal, and no sump may be in an elevator machine room.
Water treatment device waste is protected under SPS 382.41, and its tubing must meet Table 384.30-8 or 384.30-11 standards.