4.2 Trap-to-Vent Distances (Table 382.31-1)
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
4.2 Trap-to-Vent Distances (Table 382.31-1)
Key Takeaways Explain This Topic AI
Table 382.31-1 sets the maximum developed length from trap weir to vent based on fixture drain diameter, pitch, and how the vent connects.
A 1-1/2 inch fixture drain to a vent on horizontal piping may be 6 feet at 1/4 inch per foot but only 3 feet at 1/2 inch per foot; 1/8 inch per foot is not permitted for drains under 3 inches.
When the vent is on vertical piping, a sanitary tee allows longer distances than a wye pattern fitting; a 2-inch drain at 1/4 inch per foot is 6 feet with a sanitary tee and 4.5 feet with a wye.
A vent may not connect within 2 pipe diameters of the trap weir (SPS 382.31 (9) (b)).
For integral traps the distance is measured from the fixture outlet; for a floor-outlet water closet, from where the fixture drain turns horizontal.
Last updated: October 2026
Why the distance is limited
A fixture drain flowing full can siphon its own trap if the vent is too far away. The drop between the trap weir and the vent opening must stay small enough that the seal is not pulled. Wisconsin controls this with Table 382.31-1 , "Maximum Developed Length Between Vent and Trap." SPS 382.31 (9) (a) requires each fixture trap to be protected by a vent within those limits.
Where the measurement starts and ends
Separate traps : from the trap weir to the vent connection (9) (a) 1.
Integral traps (water closets, many urinals): from the fixture outlet to the vent connection (9) (a) 2.
Floor-outlet water closet : the point where the fixture drain turns horizontal counts as the fixture outlet.
Minimum distance : a vent may not connect within 2 pipe diameters of the trap weir (9) (b). On a 1-1/2 inch arm, the vent must be at least 3 inches downstream of the weir.
Diameters are chosen from the smallest drain pipe installed downstream of the trap serving the fixture (footnote a).
Table 382.31-1 (feet)
Fixture drain (in.) Horizontal: 1/8 Horizontal: 1/4 Horizontal: 1/2 Vertical, sanitary tee: 1/8 Vertical, sanitary tee: 1/4 Vertical, sanitary tee: 1/2 Vertical, wye: 1/8 Vertical, wye: 1/4 Vertical, wye: 1/2
- 1-1/4 NP 5.0 2.5 NP 3.5 2.0 NP 1.5 1.0
- 1-1/2 NP 6.0 3.0 NP 5.0 3.0 NP 4.0 2.0
- 2 NP 8.0 4.0 NP 6.0 4.0 NP 4.5 4.0
- 3 24 12.0 6.0 10.0 8.0 6.0 8.0 6.0 6.0
- 4 32 16.0 8.0 12.0 10.0 8.0 10.0 8.0 8.0
Pitch is in inches per foot. NP = not permitted. Lengths for fixture drains over 4 inches need department approval. The "wye pattern fitting" means a tee-wye, a combination wye and eighth bend, or a wye plus eighth bend with no more than 1 inch between them (footnote b).
Three patterns to notice
Steeper pitch means a shorter allowed length. Doubling the pitch from 1/4 to 1/2 inch per foot cuts every allowance in half or more, because the drop across the arm grows quickly and can put the trap weir above the vent opening.
1/8 inch per foot is allowed only for 3 and 4-inch fixture drains. Smaller drains must be pitched at 1/4 or 1/2 inch per foot (and the branch pitch rule in SPS 382.30 (5) requires 1/4 inch per foot for drains 2 inches or less anyway).
Vertical connections are shorter than horizontal ones , and a wye-pattern connection to vertical piping is shortest of all.
Worked examples
Lavatory. A 1-1/4 inch lavatory drain is pitched 1/4 inch per foot to a vent on horizontal drain piping. The table allows 5.0 feet . If the arm instead drops into a vertical drain through a sanitary tee, the limit is 3.5 feet .
Shower. A 2-inch shower drain runs 7 feet at 1/4 inch per foot to a sanitary tee in a vertical wet-vented drain. The limit is 6.0 feet , so 7 feet fails. The fix is to add a vent closer to the trap, or reroute so the vent is on horizontal piping (8.0 feet allowed).
Water closet. A floor-outlet water closet on a 3-inch fixture drain is measured from where the drain turns horizontal under the floor. At 1/4 inch per foot to a vent on horizontal piping, the limit is 12 feet . At 1/8 inch per foot it is 24 feet , which is why long water closet runs are often pitched at the minimum.
Where else Table 382.31-1 applies
The same limits are written into other venting methods:
Common vents on horizontal branches: the drain from the common vent to the farthest trap must meet (9).
Wet vents : both fixture drains in a vertical wet vent must meet (9). The lower drain's connection is treated as the vent connection.
Circuit vents : each fixture drain's connection to the circuit-vented branch is treated as its vent connection.
Combination drain and vent systems : fixture drains to the stack, and building drain branches, may not exceed the table.
Garage catch basins : trapped drains discharging to a basin must be within the table or be vented.
Chemical waste basins : the drain between a submerged basin inlet or outlet and the vent must meet the table.
Exam strategy
Check three things in order before you read the table: the diameter (smallest pipe downstream of the trap), the pitch , and the type of vent connection (horizontal, vertical sanitary tee or vertical wye). Most wrong answers come from reading the horizontal column for a vent that actually connects to a vertical pipe.