Study guide

3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves

Wisconsin Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Rules & Code Administration

1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards

2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)

2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers

3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)

3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses

4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices

4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)

5 Chapter 5: Water Supply Systems (SPS 382.40)

5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks

6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)

6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration

7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)

7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances

8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)

8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)

9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping

10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers

11 Chapter 11: Special Plumbing Installations & Water Reuse

11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves

Key Takeaways Explain This Topic AI

A return vent rises as high as possible under the fixture enclosure, returns downward and connects with a wye; piping below the floor uses drainage fittings sloped 1/4 inch per foot with cleanouts.

A combination drain and vent stack may serve no more than 3 fixtures, each on a separate floor and each 2.0 dfu or less, sized by Table 382.31-5 (0.5 dfu = 1-1/2 in., 1.0 = 2 in., 2.0 = 3 in.).

A building drain used as a combination drain and vent may take no more than 2 water closets, and floor drain traps on it must be at least 3 inches.

An AAV must sit within 15 degrees of vertical, at least 4 inches above the horizontal pipe served, no more than 20 inches below the flood rim and at least 6 inches above insulation.

AAVs are prohibited in health care facilities, licensed restaurant kitchens, residential bedrooms, daycares, sumps, POWTS tanks and FOG treatment devices, among others.

Last updated: October 2026

Return vents for islands and enclosures (SPS 382.31 (12))

A kitchen island sink has no wall to carry a vent up. Wisconsin's answer is the return vent :

Extend an individual vent, vertical wet vent or common vent as high as possible under the fixture enclosure , then return it vertically downward and connect it to the fixture drain or branch drain with a wye-pattern fitting .

Horizontal vent piping connects to the vertical section of the fixture vent and runs to a point where it can rise to a vent terminal or join another vent.

All vent piping below the floor must use drainage fittings and slope at least 1/4 inch per foot to the drainage point, because it can fill with water during a stoppage.

Provide cleanouts on the vent piping under SPS 382.35.

Combination drain and vent systems (SPS 382.31 (17))

A combination drain and vent system uses oversized drain piping to carry both water and air. Wisconsin permits four types.

Stacks

  • Condition Rule
  • Fixture count No more than 3 fixtures, each on a separate floor
  • Fixture load Each fixture 2.0 dfu or less; no urinals into the combination portion
  • Offsets None above the lowest fixture drain connection
  • Fixture drains Within Table 382.31-1 developed lengths

Size (Table 382.31-5) Largest fixture 0.5 dfu: 1-1/2 in.; 1.0 dfu: 2 in.; 2.0 dfu: 3 in.

A second stack option serves one kitchen sink above one wall-outlet fixture of 2 dfu or less in a dwelling unit, with no other fixtures. The stack is at least 2 inches below the sink and 4 inches below the lower fixture, or 3 inches for its entire length below the sink. It may not offset above the lower fixture's connection.

Building drains and subdrains

A building drain may serve as a combination drain and vent for floor drains and floor-outlet fixtures if:

A vent or drain of at least 2 inches connects upstream of any building drain branch.

No more than 2 water closets connect through building drain branches.

The building drain between the branch and the upstream vent is one pipe size larger than Table 382.30-3 requires, and at least 3 inches . The vent is at least half that diameter and at least 2 inches.

Floor drain and floor-outlet fixture traps (other than water closets) are at least 3 inches .

No branch connects within 20 pipe diameters downstream of a stack base fitting.

Branch pitch and length meet Table 382.31-1.

Island laboratory sinks and elevator threshold drains

Island laboratory sinks may use a horizontal combination drain one size larger than Table 382.30-2 requires. It needs a 2-inch minimum vent or drain stack upstream, 3-inch fixture drains, individual connections, and a looped vent under each sink with a cleanout. Elevator threshold drain stacks are a minimum of 6 inches with 4-inch traps, no offsets, and a vent at least 3 inches (and half the largest stack diameter) rising from above the highest branch.

Air admittance valves (SPS 382.31 (17m))

An air admittance valve (AAV) opens to admit air on negative pressure and closes by gravity. Wisconsin treats it only as a termination point. Amendments to (17m) took effect September 1, 2026 under CR 26-019.

Where an AAV may serve. It may terminate a branch vent, circuit vent, common vent, individual vent, wet vent or combination drain and vent system. It may serve a pumped-discharge clothes washer standpipe only when the fixture drain downstream of the vent point is at least 3 inches. A branch with AAV-vented fixtures that connects to a stack with 4 or more branch intervals above it needs a relief vent between the most downstream fixture and the stack.

Where an AAV may not be the vent termination (selected items from the 18-item list):

  • Negative-pressure areas, laboratories and commercial parking structures
  • Vents that relieve positive pressure, and stack vents serving 2 or more branch intervals
  • Vent stacks required by SPS 382.31 (4) (a), and vents serving sumps
  • Chemical waste fixtures, POWTS holding or treatment tanks, and FOG treatment devices
  • Supply or return air plenums, enclosed stairwells, and pits or vaults below grade
  • Clean rooms, health care facilities, licensed restaurant kitchens, residential bedrooms and daycares

Sizing. Table 382.31-6 limits the developed length from the fixture to the AAV:

Max dfu 1-1/4 in. 1-1/2 in. 2 in.

  • 1 35 ft no limit no limit
  • 3 28 ft 140 ft no limit
  • 6 NP 100 ft 200 ft
  • 20 NP 60 ft (no more than 2 water closets) 110 ft
  • 160 NP NP 25 ft

Installation. The AAV must be:

Vertical, within plus or minus 15 degrees of plumb.

At least 4 inches above the top of the horizontal pipe it serves.

No more than 20 inches below the flood rim of any fixture it serves.

At least 6 inches above insulation.

Accessible, in a space that admits air.

Backed by at least one 3-inch or larger vent on the same building drain that extends outdoors.

The vent system an AAV serves may offset horizontally less than 36 inches above the floor if it doesn't connect to another vent.

Testing and documentation. Test the AAV before or after installation at 1 inch of water column . If the pressure falls 0.5 inch or less in 1 minute , it passes. The contractor must give the owner a copy of the manufacturer's written AAV description.

Loading diagram... Is an AAV allowed here?