3.1 Vent Stacks, Relief Vents & Vent Sizing Tables
Wisconsin Journeyman Plumber Exam
Track your progress as you read
Finished sections get a check mark.
1 Chapter 1: Licensing, Exam Rules & Code Administration
1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards
2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)
2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers
3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses
4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices
4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)
5 Chapter 5: Water Supply Systems (SPS 382.40)
5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks
6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)
6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration
7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)
7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances
8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)
8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)
9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)
9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment
10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping
10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers
11 Chapter 11: Special Plumbing Installations & Water Reuse
11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration
3.1 Vent Stacks, Relief Vents & Vent Sizing Tables
Key Takeaways Explain This Topic AI
Vents must limit the pneumatic pressure differential on any trap seal to 1 inch of water column (SPS 382.31 (3) (a)).
A vent stack and a stack vent are required for any drain stack of 5 or more branch intervals; stacks of more than 10 branch intervals need a relief vent at each tenth interval.
A building drain that drops 12 feet or more at an angle of 45 degrees or more needs a relief vent connected within 2 feet upstream of the drop.
Vents connecting to other vents must do so at least 38 inches above the floor and at least 2 inches above the flood level rim of the highest fixture served.
Table 382.31-3 sizes branch, individual, common and circuit vents by dfu and developed length; a 1-1/4 inch vent may serve no water closets.
Last updated: October 2026
The performance rule behind every vent table
SPS 382.31 (3) (a) states the goal: every trap and trapped fixture gets an individual vent unless the chapter allows another method. Vent systems must be designed so that a trap seal "shall be subject to a maximum pneumatic pressure differential equal to one inch of water column." Every table in this chapter exists to meet that 1-inch limit.
Stacks that must be vented
Situation Requirement
Every gravity sanitary building sewer At least one stack, minimum 3 inches, from building drain to vent terminal or vent header (3) (b)
- Drain stack of 5 or more branch intervals Vent stack plus stack vent (4) (a)
- Drain stack of more than 10 branch intervals Relief vent at each tenth interval (6)
Offset of 30 to 45 degrees with a branch within 2 ft, 5 or more intervals above Offset venting per (5) (a), unless stack and offset are sized as building drain
Offset over 45 degrees with 5 or more intervals above Vent upper section as its own stack, plus a yoke vent on the lower section (5) (b)
Building drain dropping 12 ft or more at 45 degrees or more Relief vent (7)
Vent stack connections. The vent stack connects to the drain stack at or below the lowest branch drain connection, using a wye-pattern fitting in a vertical part of the stack. The vent stack and stack vent then either run to a vent terminal, join a vent stack that does, or connect to a stack vent at least 6 inches above the flood level rim of the highest fixture on the drain stack. Where a vent stack joins another vent, the joint must be at least 38 inches above the next higher floor where vented fixtures are located, and never less than 2 inches above the highest flood level rim served.
Relief vents for tall stacks. On stacks over 10 intervals, the relief vent's lower end connects with a wye below the horizontal branch on that floor, and its upper end ties to the vent stack at least 38 inches above the next higher floor with fixtures on the stack.
Building drain relief vents. The relief vent connects with a wye within 2 feet upstream of the top of the change in elevation. Its connection to another vent is at least 38 inches above the next higher floor. It must be at least half the diameter of the building drain.
Vent grade and connection heights (SPS 382.31 (15))
All vents must be graded to drain back to a drain pipe by gravity.
Except for wet vents, a vent connects to horizontal drain piping above the horizontal centerline of the drain.
A vent serving a wall-outlet fixture may not run horizontally lower than 36 inches above the floor , and never below the highest flood level rim it serves (return vents and combination systems excepted).
Vent piping may not connect to a branch vent lower than 38 inches above the floor , and never less than 2 inches above the highest flood level rim served.
Sizing stack vents and vent stacks (Table 382.31-2)
Stack vents and vent stacks are sized from the diameter of the drain stack at its base and the developed length of the vent. The developed length of a stack vent is measured from the highest drain branch connection to the vent terminal or header. For a vent stack, it is measured from its base connection to the terminal or header.
- Drain stack at base (in.) 1-1/2 vent 2 vent 3 vent 4 vent 5 vent
- 2 50 ft 150 ft no limit - -
- 3 NP 50 ft 400 ft no limit -
- 4 NP 20 ft 180 ft 700 ft no limit
- 5 - NP 50 ft 200 ft 700 ft
- 6 - NP 20 ft 70 ft 200 ft
A 1-1/2 inch stack vent may serve no more than 2 water closets or similar flush-action fixtures of 4 or more dfu. Yoke vents are sized as vent stacks.
Sizing individual, common, branch and circuit vents and vent headers (Table 382.31-3)
These vents are sized by the dfu they serve and the developed length from the farthest fixture drain served to the point where the vent joins a larger vent or the terminal.
dfu served 1-1/4 in. 1-1/2 in. 2 in. 3 in. 4 in.
- 2 50 ft no limit - - -
- 4 40 ft 200 ft no limit - -
- 8 NP 150 ft 250 ft no limit -
- 10 NP 100 ft 200 ft no limit -
- 24 NP 50 ft 150 ft no limit -
- 42 NP 30 ft 100 ft 500 ft no limit
- 72 - NP 50 ft 400 ft no limit
- 240 - NP 40 ft 250 ft no limit
- 500 - NP 20 ft 180 ft 700 ft
Footnotes: a 1-1/4 inch vent may serve no water closets , and a 1-1/2 inch vent may serve no more than 2 water closets or similar fixtures of 4 or more dfu. A vent header uses the sum of the dfu of all stacks it vents and may not be smaller than any vent connecting to it.
Worked example 1. A branch vent serves 20 dfu with a developed length of 120 feet. Use the 24-dfu row: 1-1/2 inch allows only 50 feet, 2-inch allows 150 feet, so the vent is 2 inches .
Worked example 2. A 4-inch drain stack needs a stack vent with a 100-foot developed length. In Table 382.31-2 a 2-inch vent is limited to 20 feet and a 3-inch vent to 180 feet, so use 3 inches .
Relief vent sizing. A relief vent for a circuit-vented branch must be at least half the branch diameter. A relief vent for a horizontal wet vent must be at least 1-1/2 inches. Lengths for both come from Table 382.31-3.