Study guide

3.2 Common Vents, Wet Vents & Circuit Vents

Wisconsin Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Rules & Code Administration

1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards

2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)

2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers

3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)

3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses

4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices

4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)

5 Chapter 5: Water Supply Systems (SPS 382.40)

5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks

6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)

6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration

7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)

7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances

8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)

8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)

9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping

10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers

11 Chapter 11: Special Plumbing Installations & Water Reuse

11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

3.2 Common Vents, Wet Vents & Circuit Vents

Key Takeaways Explain This Topic AI

A common vent on a vertical drain may serve at most 2 fixtures whose drains connect at the same elevation (SPS 382.31 (11) (a)).

A horizontal wet vent formed by lavatory drains may serve no more than 2 bathtubs or showers and 2 water closets, and only in nonpublic bathroom groups.

A wet vent must be at least 2 inches in diameter, and no more than 4 dfu may discharge into a 2-inch wet vent.

A circuit vent may serve 2 to 8 wall-outlet or 2 to 8 floor-outlet fixtures and connects between the 2 most upstream fixtures; 4 or more fixtures require a relief vent.

The drain served by a circuit vent may not diminish in size between the most downstream fixture drain and the circuit vent connection.

Last updated: October 2026

Why these methods exist

An individual vent on every trap is the default (SPS 382.31 (3) (a)), but it's expensive in walls and ceilings. Wisconsin permits common vents , wet vents , circuit vents , return vents , combination drain and vent systems and limited air admittance valves as alternatives. Each is allowed only inside its own fence of conditions. Exam questions usually test one condition: a fixture count, a minimum diameter or a dfu limit.

Common vents (SPS 382.31 (11))

Vertical drains. A common vent may serve a maximum of 2 fixtures when both fixture drains connect to a vertical drain at the same elevation .

If the connection is a sanitary tee with a side inlet, the centerline of the side inlet may not be below the centerline of the larger opening.

A double sanitary tee may not be used for a blowout-type fixture, a kitchen sink with a food waste grinder or pumped-discharge appliance, or a clothes washer served by a common vent. Their discharge can blow across into the opposite drain.

Horizontal branches. The drains from 2 wall-outlet fixtures, each 1 dfu or less , or from the 2 traps of a kitchen sink (with or without a dishwasher), may join a horizontal branch without individual vents if a common vent connects downstream of both fixture drains. Both fixture drains must be the same diameter, and the developed length from the vent to the farthest trap must meet Table 382.31-1.

Vertical wet vents (SPS 382.31 (13) (a))

When 2 wall-outlet fixtures on the same floor connect to the same vertical drain at different elevations, the lower fixture drain may be wet vented by the drain of the upper fixture if:

No other fixture discharges into the vertical drain above or between the two (fixtures may connect below).

A branch vent connects immediately above the higher fixture drain connection.

The drain between the 2 fixtures is at least one pipe size larger than the upper fixture drain and not smaller than 2 inches .

Both fixture drains meet the trap-to-vent distances of Table 382.31-1.

The higher fixture is not a water closet .

Horizontal wet vents for bathroom groups (SPS 382.31 (13) (b))

This is the classic house-bathroom arrangement. The drain from a lavatory or lavatories, which are individually or common vented, may serve as the wet vent for not more than 2 bathtubs or showers and not more than 2 water closets :

  • Condition Rule
  • Occupancy All fixtures in nonpublic bathroom groups

Bathtubs or showers Two tubs or showers connect independently to the common horizontal drain, downstream of the lavatory's vertical drain

Water closets 1 or 2 may connect; 2 water closets connect independently at the same point

Relief vent Required with 2 tubs or showers plus 2 water closets, unless the wet-vented drain connects to a stack with no drain connections above it

  • Wet vent size At least 2 inches; no more than 4 dfu into a 2-inch wet vent
  • Branch vent Connects immediately above the highest fixture drain; sized per SPS 382.31 (14)
  • Other fixtures No other fixtures may discharge into or be served by the wet vent

Where required, the relief vent connects downstream of the water closet drains and upstream of any other fixture drain, and it must be at least 1-1/2 inches.

Worked check. Two lavatories (1 dfu each) discharge into the 2-inch wet vent, for 2 dfu, which is within the limit. Four lavatories would reach the 4-dfu maximum for a 2-inch wet vent, and a fifth would require a larger wet vent. Adding a kitchen sink or clothes washer to the lavatory drain is prohibited outright, because no other fixtures may discharge into or be served by the wet vent.

Other wet vents (SPS 382.31 (13) (c))

An individual vent serving a floor-outlet fixture, a common vent for floor-outlet fixtures, a circuit vent, or a relief vent for a circuit-vented or wet-vented drain may itself act as a wet vent if:

No more than 2 wall-outlet fixtures, each 1 dfu or less , drain into it.

The wet vent is at least 2 inches .

The fixtures draining into it are on the same floor as the fixtures it vents.

The branch vent it joins is sized under SPS 382.31 (14).

Circuit venting (SPS 382.31 (10))

A circuit vent may serve a horizontal drain with at least 2 but not more than 8 wall-outlet fixtures , or 2 to 8 floor-outlet fixtures, on the same branch. Blowout-type fixtures and wall-outlet carrier water closets are excluded.

The circuit vent connects to the horizontal drain between the 2 most upstream fixtures .

A circuit-vented drain with 4 or more fixtures needs a relief vent downstream of the most downstream circuit-vented fixture and upstream of any other drain connection.

Two circuit-vented branches serving 8 fixtures (4 on each) need at least one relief vent, unless they drain to a stack with no connections above. One relief vent can serve both if it is downstream of where they join.

The circuit-vented drain may not diminish in size from the most downstream fixture drain (or from the relief vent) to the circuit vent connection.

Each fixture drain must meet the trap-to-vent limits of Table 382.31-1, measured to its connection with the circuit-vented branch.

Extra wall-outlet fixtures of 1 dfu or less may discharge into the branch if they have their own individual or common vents.

The relief vent for a circuit-vented branch must be at least half the branch diameter . The circuit vent itself is sized from Table 382.31-3.

Worked example. Six floor-outlet water closets in a row on a 4-inch branch: the circuit vent connects between closets 1 and 2 (the most upstream). Because there are 4 or more fixtures, a relief vent of at least 2 inches connects just downstream of closet 6. Six public closets carry 36 dfu, so with a 60-foot developed length the circuit vent from the 42-dfu row of Table 382.31-3 is at least 2 inches (2-inch limit 100 feet). A 1-1/2 inch vent would fail both the 30-foot length and the 2-water-closet limit.

Loading diagram... Choosing an alternative to individual vents