5.1 Water Supply Fixture Units (WSFU) & Demand

Wisconsin Journeyman Plumber Exam

Track your progress as you read

Finished sections get a check mark.

1 Chapter 1: Licensing, Exam Rules & Code Administration

1.1 Wisconsin Plumbing Credentials, Scope & Supervision (Ch. 145, SPS 305) 1.2 The Journeyman Exam: Format, Fees, Retakes & Permitted References 1.3 Plan Review, Plan Approval & Product Approvals (SPS 382.20) 1.4 Testing, Inspection, Maintenance & Repairs (SPS 382.21, 382.22) 1.5 Code Structure, Key Definitions, Basic Principles & Referenced Standards

2 Chapter 2: Sanitary Drainage Systems (SPS 382.30)

2.1 Drainage Fixture Units (DFU) & Load Values 2.2 Horizontal Branch Drains, Pitch & Changes in Direction 2.3 Drain Stacks, Branch Intervals & Stack Offsets 2.4 Building Drains, Building Sewers & Private Interceptor Main Sewers

3 Chapter 3: Venting Systems & Cold-Climate Vent Terminals (SPS 382.31)

3.1 Vent Stacks, Relief Vents & Vent Sizing Tables 3.2 Common Vents, Wet Vents & Circuit Vents 3.3 Return Vents, Combination Drain & Vent Systems & Air Admittance Valves 3.4 Vent Terminals, Frost Closure & Prohibited Vent Uses

4 Chapter 4: Traps, Indirect Waste & Wastewater Treatment Devices

4.1 Fixture Traps, Trap Seals & Direct Fixture Connections 4.2 Trap-to-Vent Distances (Table 382.31-1) 4.3 Indirect & Local Waste Piping, Air Gaps & Receptors 4.4 Interceptors, Catch Basins & Chemical Waste Treatment (SPS 382.34)

5 Chapter 5: Water Supply Systems (SPS 382.40)

5.1 Water Supply Fixture Units (WSFU) & Demand 5.2 Sizing Water Distribution Piping: Pressure, Friction & Velocity 5.3 Control Valves, Thermal Expansion, Water Hammer & Pipe Identification 5.4 Water Heaters, Relief Valves, Hot Water Delivery & Temperature Control 5.5 Water Services, Private Water Mains, Disinfection & Storage Tanks

6 Chapter 6: Cross-Connection Control & Backflow Prevention (SPS 382.41)

6.1 Cross-Connection Fundamentals, Hazard Classes & Pressure Conditions 6.2 Backflow Devices & Assemblies: Table 382.41-1, Limits & Installation 6.3 Assembly Registration, DSPS Tags, Annual Testing & Tester Registration

7 Chapter 7: Plumbing Fixtures, Fittings & Appliances (SPS 384.20)

7.1 Fixture Construction, Clearances, Shower Size & Safing 7.2 Water-Conserving Fixtures, Faucets & Fixture Supply Connectors 7.3 Water Heaters, Water Treatment Devices & Other Plumbing Appliances

8 Chapter 8: Piping Materials, Joints & Supports (SPS 384.30, 384.40, 382.60)

8.1 Approved Piping Materials by Service & Lead-Free Rules 8.2 Joints, Connections & Transitions Between Materials (SPS 384.40) 8.3 Hangers, Supports & Protection of Piping (SPS 382.60)

9 Chapter 9: Private Onsite Wastewater Treatment Systems (SPS 383, 385 & Component Manuals)

9.1 POWTS Regulation, Sanitary Permits, Plan Review & Inspection 9.2 Soil & Site Evaluation and In Situ Soil Parameters (SPS 385, SPS 383.44) 9.3 Design Flow, Septic & Holding Tanks and Tank Construction 9.4 Dispersal Components & the DSPS Component Manuals 9.5 POWTS Setbacks, Management, Maintenance Reporting & Abandonment

10 Chapter 10: Cleanouts, Stormwater, Sumps & Multipurpose Piping

10.1 Cleanouts & Manholes (SPS 382.35) 10.2 Stormwater & Clearwater Systems (SPS 382.36) 10.3 Sanitary Sumps, Ejectors & Discharge Points (SPS 382.30 (10), 382.38) 10.4 Multipurpose Piping Systems & NFPA 13D Residential Sprinklers

11 Chapter 11: Special Plumbing Installations & Water Reuse

11.1 Health Care & Related Facilities (SPS 382.50) 11.2 Manufactured Homes, Campgrounds, RV Parks & Dump Stations 11.3 Water Reuse, Plumbing Treatment Standards & Stormwater Infiltration

5.1 Water Supply Fixture Units (WSFU) & Demand

Key Takeaways Explain This Topic AI

Nonpublic fixtures use Table 382.40-1b: a lavatory is 1.0 wsfu, a kitchen sink 1.5, a gravity-tank water closet 2.0 and a flushometer water closet 6.0.

A nonpublic bathroom group with bathtub, lavatory and flush-tank water closet is 4.0 wsfu total; with a flushometer water closet it is 8.0.

Public fixtures use Table 382.40-2, where a gravity-tank water closet is 3.0 wsfu and a flushometer water closet 6.5.

Table 382.40-3 converts wsfu to gpm on separate curves; 20 wsfu is 35 gpm on the flushometer curve but 14 gpm on the flush-tank curve.

Continuous-flow equipment is added in gpm at its anticipated flow rate, not converted through fixture units (SPS 382.40 (6) (b)).

Last updated: October 2026

The load factor for water piping

SPS 382.40 (6) (a) says the load factor for intermittent fixtures "shall be computed in terms of water supply fixture units as specified in Tables 382.40-1b and 382.40-2." Fixture units are then converted to gallons per minute with Table 382.40-3 (or Table 382.40-3e for treatment devices). The water side is completely separate from the drainage dfu values in Table 382.30-1. A lavatory is 1 dfu and also 1.0 wsfu, but a nonpublic water closet is 4 dfu and only 2.0 wsfu (flush tank).

Each table gives hot, cold and total columns. Use the hot or cold column when sizing piping that carries only that water, and the total column for the building supply and water service.

Nonpublic fixtures (Table 382.40-1b)

  • Fixture Hot Cold Total
  • Automatic clothes washer 1.0 1.0 1.5
  • Bathtub, with or without shower head 1.5 1.5 2.0
  • Dishwashing machine 1.0 - 1.0
  • Hose bibb, 1/2 inch - 3.0 3.0
  • Hose bibb, 3/4 inch - 4.0 4.0
  • Kitchen sink 1.0 1.0 1.5
  • Laundry tray 1.0 1.0 1.5
  • Lavatory 0.5 0.5 1.0
  • Shower, per head 1.0 1.0 1.5
  • Water closet, flushometer - 6.0 6.0
  • Water closet, gravity flush tank - 2.0 2.0
  • Manufactured home - 15 15
  • Bathroom group: tub, lavatory, water closet (flush tank) 2.0 3.5 4.0
  • Bathroom group: tub, lavatory, water closet (flushometer) 2.0 7.5 8.0
  • Bathroom group: shower stall, lavatory, water closet (flush tank) 1.5 3.0 3.5
  • Bathroom group: shower stall, lavatory, water closet (flushometer) 1.5 7.0 7.5

Fixtures not listed may be assigned a value by comparison with a listed fixture that uses water at similar quantities and rates.

Public fixtures (Table 382.40-2), selected values

  • Fixture Hot Cold Total
  • Lavatory 0.5 0.5 1.0
  • Shower, per head 2.0 2.0 3.0
  • Bathtub 2.0 2.0 3.0
  • Clothes washer, individual commercial 2.0 2.0 3.0
  • Kitchen and food preparation sink, per faucet 2.0 2.0 3.0
  • Service sink 2.0 2.0 3.0
  • Flushing-rim sink - 7.0 7.0
  • Drinking fountain - 0.25 0.25
  • Urinal, syphon jet / washdown - 4.0 / 2.0 4.0 / 2.0
  • Water closet, flushometer - 6.5 6.5
  • Water closet, gravity flush tank - 3.0 3.0
  • Wall hydrant, 1/2 inch / 3/4 inch, hot and cold mix 2.0 / 3.0 2.0 / 3.0 3.0 / 4.0

Commercial dishwashers and large-capacity commercial washers use the manufacturer's gpm (footnote b).

Converting wsfu to gpm (Table 382.40-3)

The conversion has two curves. Use the flushometer column when the system is predominantly flushometer water closets or syphon-jet urinals, and the flush tank column when it is predominantly flush-tank closets or washdown urinals.

  • wsfu gpm, predominantly flushometer gpm, predominantly flush tank
  • 4 10 4
  • 10 27 8
  • 20 35 14
  • 30 40 20
  • 50 51 28
  • 100 68 42
  • 200 92 65
  • 500 142 125
  • 1,000 208 208

The curves meet at 1,000 wsfu. Values between rows may be interpolated . Example: 15 wsfu on the flush-tank curve lies halfway between 8 and 14 gpm, or 11 gpm.

Table 382.40-3e is a separate conversion for water treatment devices serving an individual dwelling (for example, 8 wsfu = 6.5 gpm, 40 wsfu = 9 gpm). It may not be used for hose bibbs, hydrants or high-flow fixtures. Devices that treat water to meet Table 382.70-1 use Table 382.40-3 instead.

Continuous-flow devices (SPS 382.40 (6) (b))

Equipment demanding a continuous flow, such as a cooling tower makeup, a process line or a lawn irrigation zone, is computed at its anticipated flow rate in gpm . Add that gpm to the gpm you get from converting the intermittent fixtures. Don't convert it to fixture units.

Worked example: a single-family home

  • Fixture wsfu (total)
  • 2 bathroom groups, tub/lav/flush-tank closet 2 x 4.0 = 8.0
  • Kitchen sink 1.5
  • Dishwashing machine 1.0
  • Clothes washer 1.5
  • Laundry tray 1.5
  • 2 hose bibbs, 1/2 inch 2 x 3.0 = 6.0
  • Total 19.5 wsfu

The house is predominantly flush tank, so 19.5 wsfu converts to about 13.7 gpm (interpolating between 10 wsfu = 8 gpm and 20 wsfu = 14 gpm). The hot-water piping carries only the hot column: 2 x 2.0 + 1.0 + 1.0 + 1.0 + 1.0 = 8.0 wsfu .

Water heater sizing alternate (SPS 382.40 (6) (c))

For a water heater serving a single residence or living unit used by one household, an alternate method is allowed:

Minimum heater flow rate = 0.65 x the calculated hot-water gpm from Tables 382.40-1b and 382.40-3.

A storage heater's flow rate may be based on 70 percent usable storage plus recovery rate, with a 10-minute minimum draw.

An instantaneous heater must deliver a rise that provides 110 degrees F at the terminal fixture.

The method may not be used for heaters serving high-flow fixtures (more than 4 gpm at 80 psig), hose bibbs, hydrants or fixtures needing 1/2-inch or larger supplies, or for sizing hot-water distribution piping.

Exam traps

Mixing up dfu (drainage) and wsfu (supply) values.

Using the flushometer curve for a house; a house is predominantly flush tank.

Using the nonpublic table for a restaurant or office, where public values (water closet 3.0 tank or 6.5 flushometer) apply.

Loading diagram... From fixtures to design flow