Egypt Engineering Consultant Mechanical
Egypt Engineering Consultant — Mechanical (استشاري ميكانيكا)
Full question bankEnglish
Exam overviewPractice session
An office space in New Cairo has a calculated peak sensible cooling load of 48 kW. The indoor design condition specified by the Egyptian Code for Air Conditioning (ECP 301) is 24°C dry bulb. If supply air enters the room at 14°C dry bulb and standard air properties apply (density ρ = 1.20 kg/m³, specific heat c_p = 1.005 kJ/kg·K), what is the required supply airflow rate?
Loading your practice session…