During a combustion check on a non-condensing natural gas boiler, a technician measures a flue gas temperature of 140°C, an ambient boiler room temperature of 20°C, and a carbon dioxide level of CO2 = 9.0%. Using the Siegert formula with coefficient k = 0.38 for natural gas (sensible heat loss Qs = k * (T_flue - T_ambient) / CO2), what is the calculated combustion efficiency (eta = 100 - Qs)?